PLEASE NOTE: As long as you are registered for this IFB you will continue to receive these notices. If you plan to not respond to this IFB with a bid submittal, you may want to access the eProcurement Marketplace and mark "No Bid." Once you have done such, you will not continue to receive any notices pertaining to this IFB.
We have received the following request for information and hereby respond following:
(1) QUESTION. “…I was looking at this project last night and realized that this is a high rise and as such the new service for the fire pump I believe has to be a two hour rated wiring. This should be brought to [the engineer’s] attention and addressed for everyone’s concern if I am correct...”
AGENCY RESPONSE. Wiring method for fire pump service and feeder shall be Mineral Insulated (MI) Cable or in Rigid Steel conduit.
We are grateful for your interest in doing business with our Agency and we look forward to receiving a bid submittal from your firm.
Regards,
Heather Kaufman
Procurement Coordinator
Note: One of the files available for downloading might be a ZIP file.