PLEASE NOTE: As long as you are registered for this IFB you will continue to receive these notices. If you plan to not respond to this IFB with a bid submittal, you may want to access the eProcurement Marketplace and mark "No Bid." Once you have done such, you will not continue to receive any notices pertaining to this IFB.
We have received the following request for information and hereby respond following:
(1) QUESTION. Question: Will the city/state require a separate service for the fire pump? If yes will we size this service according to the new electrical code? Will the primer pump be fed off this new separate service?
AGENCY RESPONSE. A separate service for the fire pump with a separate utility meter have been added to the attached documents in response to this request for information. The “jockey” pump will remain fed from the existing panel. Please see the amended drawings Attachments #1 - #4, attached hereto.
(2) CLARIFICATION. Cable routing shall be through second floor storage room as shown in added detail 3/ES1.0.
We are grateful for your interest in doing business with our Agency and we look forward to receiving a bid submittal from your firm.